current transformer

current transformer
Product Detailed
Related Categories:Sensors
Primary Current(A):5 Secondary Current(mA):2.5 Burden Rb:20 Max Current(A):50 Accuracy Class:0.2 Note:DC15.

Basic parametersPrimary Current(A)Secondary Current(mA)BurdenMax Current(A)Accuracy ClassNote
Rb(Ω)
52.520500.2DC15.9A
       
       
       
       
Current error and phase error limitsAccuracy ClassCurrent error ±(%)phase error(′) 
In the following currentsIn the following currents
0.01In≥0.05In0.01In0.05In0.2In1In2In3InImax
0.1 Class0.20.115855555
0.2 Class0.40.230151010101010
Note: When current is 0.2In~Imax, phase error(δe ) is the average of δmax and
δmin;When current is i, the phase error of i is the difference of betweenδi  and δe. (δi=δi-δe).
 When currents is 15.9A, The electric energy measurement error introduced by current transformers  is less than 3% 
Sine-half wave test
Normal Service ConditionsAmbient temp.(°C):-40°C~+70°C; Relative Humidity :≤98(25°C); Altitude :≤3000m
The main electrical performanceAnd a winding secondary winding voltage between the tolerance of not less than 3 kV, insulation resistance of not less than 1000MΩ
Reference size(mm)ABCDEFGH       
9φ6.22030.216462.230.5       
               
               